Analysis of a selected area of Wrocław in the context of cooling Devices

Juliusz Walaszczyk, Weronika Michalak

Wydział Inżynierii Środowiska, Politechnika Wrocławska

Ciepłownictwo Ogrzewnictwo Wentylacja, 2026 (1), 14-22, DOIhttps://doi.org/10.65545/COW.2026.01.03

Keywords: ventilation, air conditioning, cooling, split units, refrigerants 

Abstract 

Introduction: Nowadays, considerable emphasis is placed on improving the efficiency of devices responsible for cooling buildings and, consequently, on reducing electricity consumption. In the process of enhancing efficiency and striving for climate neutrality, it may prove valuable to understand the current stae of the cooling equipment market in urban environments. 

Aim: To provide basic knowledge about cooling technologies used in a selected district of the city of Wrocław. To assess the systems found in the city in terms of nominal cooling capacity, installation methods, and the refrigerants employed. 

Methods: Field research was carried out in the Przedmieście Oławskie district, identifying outdoor units. In addition to collecting nominal data declared by manufacturers, an estimation was made of shading and the geographical orientation of the condensers. 

Conclusions: A total of 150 outdoor units were inventoried, including 146 split or multi-split systems. The study confirms that split-type air conditioning systems are equally popular in both older and newer buildings. Most cooling systems in the surveyed area operate using the refrigerant R410A (53% of units). The second most common refrigerant is R32 (44% of devices). Cooling in the oldest buildings is designed for low energy demand and, surprisingly, utilises the most environmentally friendly technology.

Download the article in PDF format

Download the entire issue in PDF format

Bibliography

  1. Centrum Informacji o Rynku Energii. (2022). Czym jest miejska wyspa ciepła? Dostęp z 2 listopada 2025 z https://www.cire.pl/artykuly/materialy-problemowe/czym-jest-miejska-wyspa-ciepla
  2. ElSherbini, A. I., & Maheshwari, G. P. (2010). Impact of shading air-cooled condensers on the efficiency of air-conditioning
    systems. Energy and Buildings, 42(10), 1948-1951. https://doi.org/10.1016/j.enbuild.2010.05.031
  3. Gree. (b.d.). Klimatyzator split czy multi split? Dostęp z 2 listopada 2025 z https://gree.pl/baza-wiedzy/klimatyzatory/klimatyzator-split-czy-multi-split/
  4. Howarth, N., Camarasa, C., Lane, K., & Risquez Martin, A. (2023, 21 lipca). Keeping cool in a hotter world is using more energy, making efficiency more important than ever. International Energy Agency. https://www.iea.org/commentaries/keeping-cool-in-a-hotter-world-is-using-more-energy-making-efficiency-more-important-than-ever
  5. International Energy Agency. (b.d.). Space cooling. Dostęp z 2 listopada 2025 z https://www.iea.org/energy-system/buildings/space-cooling
  6. Klimatyzacja.pl. (2023). Czynniki chłodnicze stosowane w chłodnictwie. Dostęp z 2 listopada 2025 z https://www.klimatyzacja.pl/artykuly/chlodnictwo/artykuly/czynniki-chlodnicze/czynniki-chlodnicze-stosowane-w-chlodnictwie
  7. Kwidziński, K. (2025). Sierpień 2025 – Węgiel pod gruszą. Miesięcznik Forum Energii, Dostęp z 15 września 2025
    www.forum-energii.eu
  8. LG Electronics. (2020). Instrukcja montażu klimatyzatora DCxxRH.
  9. Martínez, P., Ruiz, J., Cutillas, C. G., Martínez, P. J., Kaiser, A. S., & Lucas, M. (2016). Experimental study on energy performance of a split air-conditioner by using variable thickness evaporative cooling pads coupled to the condenser. Applied Thermal Engineering, 105, 1041-1050. https://doi.org/10.1016/j.applthermaleng.2016.01.067
  10. Michalak, W. (2025). Rynek technologii chłodzenia powietrza wewnątrz pomieszczeń na terenie miasta Wrocław. Praca magisterska. Politechnika Wrocławska
  11. Naphon, P. (2010). On the performance of air conditioner with heat pipe for cooling air in the condenser. Energy Conversion and Management, 51(11), 2362-2366. https://doi.org/10.1016/j.enconman.2010.04.010
  12. Reszewski, S. (2025). Trigeneracja rozproszona w warunkach wrocławskich. Instal. 4.
  13. Sowa, J., Narowski, P.G., Rubik, M., & Ziętek, P. (2017). Budynki o niemal zerowym zużyciu energii, Politechnika Warszawska.
  14. Stefaniak, Ł., & Walaszczyk, J. (2025). Nowelizacja rozporządzenia Unii Europejskiej w sprawie F-gazów w kontekście
    globalnym oraz perspektyw stosowania alternatywnych czynników chłodniczych. Ciepłownictwo Ogrzewnictwo Wentylacja, 56. https://doi.org/10.15199/9.2025.1.2
  15. Szczęśniak, S., Karpuk, M., Stefaniak, Ł., Grabka, A., Michalak, W., Jaskóła, W., Maciewicz, M. (2024). Obowiązujące normy
    na tle rzeczywistych wartości temperatury powietrza zewnętrznego w Polsce. Ciepłownictwo, Ogrzewnictwo, Wentylacja 4(55): 20-29. https://doi.org/10.15199/9.2024.4.4
  16. Szkolenia-F-Gaz. (n.d.). Wytyczne odległości między jednostkami klimatyzacji. Dostęp z 2 listopada 2025 https://szkolenia-fgaz.pl/wytyczne-odleglosci-miedzy-jednostkami-klimatyzacji/